GVX750K500HS Galaxy VX 500kVA N+1 Redundant UPS 400V

$172,325.00

Galaxy VX 500kVA N+1 Redundant UPS 400V, Start up 5Ă—8

Highly efficient, scalable, 3-phase power protection with flexible operating modes and ECOnversion™ for large facilities, data centers, and business critical applications.

Includes: Installation guide, Start-Up Service

GVX750K500HS Galaxy VX 500kVA N+1 Redundant UPS 400V
$172,325.00

Output

Max Configurable Power (Watts)

500.0kWatts / 500.0kVA

Output Frequency (sync to mains)

50 Hz, 60 Hz

Output Frequency (not synced)

50Hz +/- 0.1% for 50Hz nominal

Other Output Voltages

380, 415, 440

Load Crest Factor

3 with THC <5% Topology Double Conversion Online Waveform type Sine wave Overload Operation 150% for 1 minute 125% for 10 minutes Output Voltage THD < 2% linear load and <3% non-linear load Input Input frequency 40 – 70 Hz Input Total Harmonic Distortion Less than 3% for full load Other Input Voltages 380, 415, 440 Maximum Short Circuit Withstand (Icw) 100.0kAmps Batteries & Runtime Battery type No internal battery – uses external battery system Nominal Battery Voltage 480V End of Discharge Battery Voltage 384 Vdc Efficiency View Efficiency Graph Communications & Management Control panel 7″ Touch Screen Display Audible Alarm Audible and visible alarms prioritized by severity Available SmartSlot™ Interface Quantity 2 Physical Maximum Height 77.56inches (1970MM, 197.0CM) Maximum Width 129.92inches (3300MM, 330.0CM) Maximum Depth 35.43inches (900MM, 90.0CM)