G5TUPS40 MGE Galaxy 5000 40 kVA Ups

Availability

Dual mains input

Increases availability by allowing the UPS to be connected to two separate power sources.

Adjustable voltage sensitivity

Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.

Frequency and voltage regulation

Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.

Generator compatible

Ensures clean, uninterrupted power to protected equipment when generator power is used.

G5TUPS40 MGE Galaxy 5000 40 kVA Ups

Output

Max Configurable Power (Watts)

36.0kWatts / 40.0kVA

Neutral Output Current

87A

Output Voltage Note

Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage

Output Voltage Distortion

Less than 2%

Output Frequency (sync to mains)

50 Hz – programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%, 60 Hz

Output Frequency (not synced)

60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal

Other Output Voltages

208, 220, 380, 400, 415, 600

Load Crest Factor

3 : 1

Topology

Double Conversion Online

Waveform type

Sine wave

Overload Operation

10 minutes @ 125% and 60 seconds @ 150%

Maximum Output Current

190

Output Voltage THD

< 1% linear load and < 2.5% nonlinear load Output Voltage Tolerance +/- 1% static and +/- 2 % at 100% load step Bypass Internal Bypass (Automatic and Manual), Optional External Bypass Input Input frequency 45 – 65 Hz Input voltage range for main operations 340 – 460 (400V), 408 – 538V Input Total Harmonic Distortion Less than 3% for full load Type of Input Protection Required 3-pole breaker Other Input Voltages 380, 400, 415, 480, 600 Maximum Short Circuit Withstand (Icw) 20.0kAmps Input Power Factor at Full Load 1.0 Batteries & Runtime Battery type No internal battery – uses external battery system Efficiency View Efficiency Graph Communications & Management Control panel Multi-function LCD status and control console Emergency Power Off (EPO) Optional