Output
Max Configurable Power (Watts)
10.0kWatts / 10.0kVA
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
50Hz, 60Hz
Output Frequency (not synced)
50Hz +/-0.1% for 50Hz nominal, 60Hz +/-0.1% for 60Hz nominal
Other Output Voltages
200, 220
Load Crest Factor
2.5
Topology
Double Conversion Online
Waveform type
Sinewave
Overload Operation
150% for 1 minute 125% for 10 minutes
Output Voltage THD
<2% linear load and <5% non-linear load Output Voltage Tolerance +/-1% after 50ms Bypass Built in static bypass Input Input frequency 40-70Hz Input voltage range for main operations 177-239V Input Total Harmonic Distortion Less than 3% at full load Other Input Voltages 200, 220 Maximum Short Circuit Withstand (Icw) 65.0kAmps Input Power Factor at Full Load 0.99 Batteries & Runtime Battery type VRLA Nominal Battery Voltage 480 End of Discharge Maximum Battery Current 27.0A End of Discharge Battery Voltage 384VDC Efficiency View Efficiency Graph Communications & Management Control panel Touchscreen LCD user interface Audible Alarm Audible and visible alarms prioritized by severity Physical Maximum Height 58.0inches (1485MM, 148.5CM)