GVSUPS50KGS Galaxy VS UPS 50kW 480V for External Batteries,

$20,864.00

Galaxy VS UPS 50kW 480V for External Batteries, Start-up 5×8

Highly efficient, easy-to-deploy 50kW, 480V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5×8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.

Includes: Dust filter, Installation guide, Integrated network management, Power modules ship installed, Start-Up Service, Top and bottom cable entry

GVSUPS50KGS Galaxy VS UPS 50kW 480V for External Batteries,
$20,864.00

Output

Max Configurable Power (Watts)

50.0kWatts / 50.0kVA

Output Voltage Distortion

Less than 3%

Output Frequency (sync to mains)

50 Hz, 60 Hz

Output Frequency (not synced)

60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal

Load Crest Factor

2.5

Topology

Double Conversion Online

Waveform type

Sine wave

Overload Operation

150% for 1 minute 125% for 10 minutes

Output Voltage THD

<1% linear load and <3% non-linear load Output Voltage Tolerance +/-1% after 50ms Bypass Built-in Static Bypass Input Input frequency 40 – 70 Hz Input voltage range for main operations 408 – 552 (480)V Input Total Harmonic Distortion Less than 3% for full load Maximum Short Circuit Withstand (Icw) 65.0kAmps Input Power Factor at Full Load 0.99 Batteries & Runtime Battery type No internal battery – uses external battery system Nominal Battery Voltage 480-576VDC End of Discharge Maximum Battery Current 135.0A End of Discharge Battery Voltage 384 Vdc Efficiency View Efficiency Graph Communications & Management Interface Port(s) GVS_Cable2ndBatCab, GVS_MBCKIT_UL, GVS_NarrowCBC_Seismic, GVS_NarrowSeismicKit, GVS_Parallel, GVS_WideCBC_Seismic, GVS_WideUPS_AirFilter, GVS_WideUPSMBC_SeismicKit, GVS_XFMRSeismicKit